HAZARDOUS AREAS
Application: Dual certified flameproof Ex d and Increased Safety Ex e indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas with all types of circular armoured cable, braided SY cables and steel tape armoured cables providing a flameproof seal on the cable outer sheath.
Gland features reversible cone to suit all applications.
Gland must be used as part of
a certified assembly in surface installations only. Gland may not be used on a group IIC Ex d Enclosure that is larger than 2000cc volume.
Certification: Group II, Category-2 (zone 1) gas group IIC confirm to EBN 60079-0:2009 & EN 60079-1:2007.
Electrical Apparatus for use in dust Zone 21 & 22 as per EN 60079- 31:2009.
Degree of protection: IP67 as per EN 60529:1991
Material:
Material of construction of cable gland is BRASS/SS304/SS316/MS
Brass: BS 2874 CZ121 / IS 319 gr.1 / SS: ASTM A314 gr. 304/304
Threads: Isometric (ISO) IS0:965 - 1 & 965 - 3, BS:3643
Operating temp: The cable sealing washer (elastomeric sealing ring) used and is suitable for operating temperature -20°C to +100°C
Note: The cable glands are suitable for SWA (Steel Wire Armoured), steel tape armoured and braid wire cable.
'W' refer to the wire diameter in a steel tape armoured cable.
'XYZ'- refer to the wire diameter In a steel tape armoured cable or braid wire cable.
Pack content: Gland(s), brass locknut(s), earth tag(s), and shroud(s)